Guide
NEC 690 solar cable sizing (AWG) — how it works
Most free off-grid solar calculators are built around IEC/metric conventions (mm² cross-sections) and don't address the National Electrical Code at all. This is a practical walkthrough of what NEC Article 690 actually requires for a DIY off-grid system — conductor sizing, grounding and bonding, and ground-fault protection — not a replacement for a licensed electrician, but enough to understand what your numbers need to satisfy.
What NEC 690 actually covers
NEC Article 690 (NFPA 70) is the section of the National Electrical Code specific to photovoltaic systems — conductor sizing and ampacity, grounding and bonding (Part V), and ground-fault protection all fall under it, alongside the general wiring rules elsewhere in the Code. An off-grid, non-utility-interactive system is still covered by 690, though some provisions written primarily for grid-tied systems apply differently or not at all — this is exactly the kind of distinction worth confirming with a licensed electrician rather than assuming from a generic guide.
AWG conductor sizing and ampacity
Conductor ampacity in the US is read from NEC Table 310.16 (the 75°C column is the common reference for most off-grid equipment terminations), then adjusted for the real installation: ambient temperature, how many current-carrying conductors are bundled together, and the run length. A cable that's the right gauge on paper at 25°C can be undersized once it's actually bundled with three other cables in a hot enclosure — the derating factors aren't optional extras, they're what makes the number correct for your install.
String cables are typically sized with a 25% safety margin on the panel's short-circuit current — standard practice independent of which code you're working under. What changes country to country is which ampacity table and which conductor markings (AWG vs mm²) you're reading the number from.
Grounding and bonding — NEC 690 Part V
For an off-grid inverter, the neutral-to-ground bonding configuration matters and depends on the inverter's topology — this isn't a detail to guess at from the datasheet alone. NEC 690 Part V (690.41, 690.43, 690.47) governs grounding and bonding for PV systems, and the equipment grounding conductor itself is sized per NEC 250.66, a separate table from the ampacity one above. Grid-interactive and off-grid systems are treated differently here, so a wiring diagram copied from a grid-tied guide won't necessarily apply as-is.
DC ground-fault protection
NEC 690.41(B) requires DC ground-fault protection (GFPD) for PV source circuits. On the AC side, dwelling circuits fall under the AFCI/GFCI requirements in NEC 210.12 and 210.8 — a different mechanism from the RCD Type B requirement used in the UK and EU, not a direct equivalent despite serving a similar purpose. If you're used to European wiring conventions, this is the point where the two codes diverge the most.
Common mistakes
Sized in AWG from the start, not converted after the fact
"La tua isola" has a dedicated US engine — AWG cable sizing against NEC Table 310.16, 120/240V inverter options, and NEC 690 regulatory notes built in, not a metric tool with units swapped afterward.
Start freeIndicative guide
An indicative pre-sizing tool, not a certified electrical design. Always have your installation verified by a licensed electrician in line with NEC 690 (National Electrical Code) before connecting anything.